The main technical parameters
1. Rated frequency: 50Hz
2. Insulation resistance: primary to secondary and primary to ground≥1000MΩ; secondary to secondary and secondary to ground≥50MΩ
3. Thermal stable current for 1 second: 75 times the rated primary current (effective value)
4. Dynamic stable current: 188 times the rated primary current (peak value)
5. See the table below for other parameters
Technical indicators
1. Rated voltage: 35KV
2. Connection method: two-element V/V connection method
3. Rated frequency: 50HZ
4. Voltage ratio: 35KV/100V
5. Voltage accuracy grade: 0.2; Current accuracy grade: 0.2S
6. Rated load: voltage 30VA; current 15VA
7. Power factor: 0.8
8. Current ratio 5-500A/5A (double transformation ratio can be made)
9. Power frequency withstand voltage: 10.5KV
10. Ambient temperature: between -25°C and 40°C, the daily average temperature does not exceed 30°C, when the temperature is 20°C, the relative temperature does not exceed 85%, and the altitude is below 1000 meters .
11. Use environment: outdoors, the installation site has no serious pollution, no serious vibration and bumpy places.
This product is composed of three-phase two-element combined transformer and instrument box. The three-phase two-element combined transformer is composed of a single-phase voltage transformer (PT) and two current transformers (CT). PT and CT are both Electromagnetic type, two PT windings are composed of V/V connection method, three-phase measuring device, and the primary windings of two CTs are connected in series with phase A and phase C of the grid respectively. In the metering part, there are two three-phase active and reactive energy meters each with an inverter to realize the electric energy measurement of forward power transmission and power transmission.
Once connected to AP1-AP2, CP1-CP2 is a large current ratio, and when connected to AP1-AP3, CP1-CP3 is a small current ratio.
For example: 50-100/5, once connected to AP1-AP2, CP1-CP2 is 100/5, once connected to AP1-AP3, CP1-CP3 is 50/5.
The product has: low magnetic density, wide load, anti-theft electricity metering box with multiple current ratios, in the state of bidirectional power transmission, no matter when the load interval changes greatly, the high precision of 0.2S can accurately measure electric energy and so on.